A 100 kVAr APFC panel is an automatic power factor correction system designed to switch capacitor-bank stages in response to changing reactive-power demand. It can be a suitable option when a facility’s measured correction requirement is close to 100 kVAr, but the rating alone does not determine whether the panel will fit the project. We recommend confirming the site’s voltage, frequency, load variation, harmonic conditions, target power factor, and installation requirements before selecting a configuration.
You can find more information on our web, so please take a look.
In this guide, we explain the panel’s main components, typical applications, specification choices, and supplier questions to resolve before ordering. SINAVA works with B2B buyers to review application requirements and discuss an appropriate power-quality product configuration. Final ratings and design details should be confirmed against the project’s electrical data and applicable installation requirements.
This guide is intended for electrical contractors, panel builders, facility engineers, procurement teams, and industrial or commercial power-system buyers. It is most useful when a project has identified a need for automatic reactive-power compensation and is considering a 100 kVAr panel. It can also help buyers prepare a more complete inquiry when the load profile or harmonic environment is not yet fully documented.
An APFC panel measures electrical conditions, typically using current and voltage sensing, and switches capacitor stages to supply reactive power as required. This can improve the power factor at the point where the panel is connected and reduce the amount of reactive current drawn from the upstream supply. The outcome depends on the system design, load behavior, measurement location, and settings.
The 100 kVAr figure is the nominal compensation capacity of the complete bank under its specified operating conditions. It does not mean that the panel continuously supplies exactly 100 kVAr, because an automatic controller usually switches stages according to demand. The panel also does not generate active energy for production equipment.
A typical assembly may include an APFC controller, capacitor stages, switching devices, protective components, a busbar system, and an enclosure. Depending on the design and application, switching may use capacitor-duty contactors or semiconductor switching devices. The supplier should state which components are included and identify any items that must be provided separately.
Capacitor stages divide the total capacity into controlled increments. For example, a 100 kVAr bank could be arranged as equal or unequal steps, but the appropriate sequence depends on how sharply and frequently the site’s reactive demand changes. Smaller increments can provide finer control, while the final arrangement must also account for switching frequency, equipment selection, and project cost.
| Specification | Why It Matters | What to Confirm |
|---|---|---|
| Rated capacity | Defines the nominal compensation available. | Confirm 100 kVAr at the specified voltage and frequency. |
| System voltage and frequency | Affects capacitor output and component selection. | Provide the site’s actual supply conditions, such as 400 V and 50 Hz where applicable. |
| Step configuration | Determines how closely the bank can follow changing demand. | Request the proposed stage sizes and switching sequence. |
| Harmonic conditions | Nonlinear loads may affect capacitor-bank application and design. | Share harmonic measurements or identify major nonlinear equipment. |
| Enclosure and installation | Influences fit, access, cooling, and site integration. | Confirm indoor or outdoor location, cable entry, and mounting needs. |
Voltage matters because capacitor reactive output changes with the voltage applied to the bank; it should not be assumed that a panel retains its nameplate kVAr at every operating voltage. As a reference calculation, a balanced three-phase 100 kVAr bank at 400 V has a reactive line current of approximately 144 A, using current equal to reactive power divided by the square root of three times line voltage. This is a nominal calculation, not a substitute for selecting protective devices or checking actual operating conditions.
Buyers should also clarify whether the quoted panel includes a detuned reactor or other harmonic-related provisions. Such provisions are not automatically required for every installation, and their suitability depends on the network’s harmonic profile and engineering assessment. Do not select a reactor configuration solely because variable-speed drives or other nonlinear loads are present; request a review of the measured or expected conditions.
A 100 kVAr APFC panel may be considered for an industrial or commercial facility where inductive loads create a fluctuating reactive-power requirement near the panel’s capacity. Examples can include motor-driven processes, pumps, compressors, HVAC equipment, and mixed production loads. These examples are starting points for assessment, not confirmation that a 100 kVAr bank will suit any particular site.
SINAVA Product Page
For relatively steady loads, a stage arrangement with fewer switching operations may be appropriate, subject to the control and equipment design. Where demand changes frequently, buyers should discuss stage granularity and switching method with the supplier. If the site experiences significant harmonics, frequent voltage variation, or rapidly changing loads, provide those details before finalizing the order.
Review utility or power-quality records, and measure reactive demand under representative operating conditions where possible. A single snapshot may not capture production changes, shift patterns, or seasonal operation. The required bank capacity should be based on the gap between the existing condition and the project’s target, rather than on a general rule of thumb.
Provide the supplier with nominal system voltage, frequency, phase arrangement, available fault information, and installation location. Include enclosure preferences, cable entry direction, access constraints, ambient conditions, and any project-specific control or communication requirements. These details help establish whether the proposed panel can be integrated into the site design.
Ask for the proposed kVAr per stage, switching device type, capacitor specifications, controller functions, and protection arrangement. Confirm how the system responds when demand is below the smallest step or changes rapidly. Request clarification of the panel scope so that included components and exclusions are visible before purchase.
Identify nonlinear loads and provide harmonic measurements when available. Discuss whether a standard capacitor bank or a design with additional harmonic mitigation is appropriate for the measured conditions. Also consider planned equipment additions, since future load changes may affect both required capacity and stage selection.
The cost of a 100 kVAr APFC panel depends on its voltage and frequency rating, step arrangement, switching devices, capacitor selection, harmonic provisions, enclosure, and requested documentation. Customization and project-specific requirements can also affect the quotation. We recommend comparing offers on a like-for-like scope rather than comparing only the headline kVAr rating.
Minimum order quantities and lead times are supplier- and configuration-dependent, so they should be confirmed in the quotation rather than assumed. For a useful inquiry, send the target rating, electrical data, application, installation conditions, quantity, required delivery location, and any technical documents. Ask the supplier to state the production schedule, shipping basis, quotation validity, and any exclusions.
At SINAVA, we support B2B buyers by discussing application data, reviewing requested panel specifications, and clarifying configuration and quotation scope. Share your electrical requirements and project conditions so our team can assess whether a 100 kVAr APFC panel is a reasonable starting point. Final selection should be verified by the project’s responsible electrical professional before installation.
A 100 kVAr APFC panel can be an appropriate solution when measured reactive-power demand, system voltage, harmonic conditions, and load variation align with its design. The most important next steps are to confirm the required compensation capacity, provide accurate site data, and review the proposed stage arrangement and protection details. Contact SINAVA with your project specifications to discuss a suitable configuration, quotation scope, and supply requirements.